Rheem Performance Platinum Liquid Propane 9.0 GPM High Efficiency Outdoor Tankless Water Heater with EcoNet : Instructions (2024)

Rheem Performance Platinum Liquid Propane 9.0 GPM High Efficiency Outdoor Tankless Water Heater with EcoNet : Instructions (1)

34

INSTALLATION INSTRUCTIONS

Venting for Direct-Vent Water Heater

DANGER:

Failure to properly vent the water heater to the outdoors

as outlined in this Venting section will result in death or

serious personal injury. To avoid the risk of fire, explosion,

or asphyxiation from carbon monoxide, NEVER operate the

water heater unless it is properly vented and has adequate

air supply for proper operation as outlined in this Venting

section. This water heater must have air supply connected

and terminated to the outdoors.

WARNING:

Refer to page 29 for required clearances to combustible

materials. Improper clearances can cause explosion or fire

resulting in death, personal injury, and/or product damage.

CAUTIONS:

Check to make sure flue gases do not recirculate into the

air intake terminal when using direct venting. If the water

heater is having service issues, flue recirculation may be a

contributing factor.

Even when the minimum vent terminal separation

distances are followed, recirculation may still occur

depending upon the location outside the building, the

distance from other buildings, proximity to corners,

weather conditions, wind patterns, and snow depth.

Periodically check to make sure that flue recirculation

is not occurring. Signs of flue gas recirculation include

frosted or frozen intake terminals and condensate in the

intake terminal and venting system.

Correction to flue recirculation may involve angling the

intake away from the exhaust terminal and increasing the

distance between them. Check to be sure the intake and

exhaust terminals are not obstructed, especially during

periods of below-freezing weather.

Venting Requirements

The installation of venting must comply with national

codes, local codes, and the vent manufacturer’s

instructions.

The vent exhaust and air intake must terminate outside

as described in these instructions. DO NOT vent this

water heater through a chimney. It must be vented

separately from all other appliances.

NOTICE:

The unit can be vented using only the following approved

vent pipe material.

Use only 2- or 3-inch diameter pipe. Refer to local

codes for restrictions on the use of InnoFlue® PP, PVC,

CPVC, or ABS pipe and fittings. All exhaust venting

materials for product installed in Canada must meet

ULC-S636.

The use of cellular core PVC (ASTM F891), cellular

core CPVC, or Radel® (polyphenolsulfone) in non-

metallic venting systems is prohibited and that

covering non-metallic vent pipe and fittings with

thermal insulation is prohibited.

Acceptable materials or equivalent:

InnoFlue® PP

PVC (Schedule 40, ASTM D-1785)

CPVC (Schedule 40, ASTM F-441)

ABS (Schedule 40, ASTM D-2661)

(not permitted for exhaust vent in Canada)

The fittings, other than the VENT TERMINAL,

should be equivalent to the following:

InnoFlue® PP

PVC (Schedule 40 DWV, ASTM D-2665)

CPVC (Schedule 40 DWV, ASTM F-438)

ABS (Schedule 40 DWV, ASTM D-2661)

(Not permitted in Canada)

Category III Stainless Steel (Proper transition part

required)

DO NOT USE Schedule 20, Cell Core, Drain Pipe,

Galvanized, Aluminum, B-Vent, or any flexible vent.

Recommended Vent Lengths

Before starting the vent installation, careful planning

should be given to the routing and termination of the

vent pipes. The length of the vent pipes (inlet and

outlet) should be kept to a minimum. Also, see pages

37–38 and 44 for vent terminal placement. Refer to the

maximum and minimum vent length charts for the pipe

sizes that can be used and the total equivalent length of

pipe that can be used. Do not exceed equivalent length

of pipe in maximum vent length chart.

Maximum Vent Length (intake/outlet) each:

Number of

90° Elbows

Maximum Length

of 2" Straight Pipe

Maximum Length

of 3" Straight Pipe

Maximum Length

of 4" Straight Pipe

1 5.0 ft. (1.5 m) 38.0 ft. (11.6 m) 94.0 ft. (28.7 m)

2 3.5 ft. (1.0 m) 36.5 ft. (11.1 m) 88.0 ft. (26.8 m)

3 2.0 ft. (0.6 m) 35.0 ft. (10.6 m) 82.0 ft. (25.0 m)

4 Not available 33.5 ft. (10.2 m) 76.0 ft. (23.2 m)

5 Not available 32.0 ft. (9.8 m) 70.0 ft. (21.3 m)

6 Not available 30.5 ft. (9.3 m) 64.0 ft. (19.5 m)

The system will not operate if there is excessive

restriction (pressure drop) in the venting system. Use

the chart above to calculate the maximum pipe run

length with the required number of elbows (e.g., a

maximum 38 ft. [12 m] of 3" vent pipe may be used

provided there is only one 90° elbow in the system).

A 90° elbow is equivalent to 1 ft. 6 in. (0.5 m) of 2" or 3"

straight pipe, and to 6 ft. (1.8 m) of 4" straight pipe. A

45° elbow is equivalent to 9” (0.25 m) of 2" or 3" straight

pipe, and to 3 ft. (0.9 m) of 4" straight pipe.

The vent termination does not count as part of the straight

pipe equivalent when determining the total vent length.

Venting

Rheem Performance Platinum Liquid Propane 9.0 GPM High Efficiency Outdoor Tankless Water Heater with EcoNet : Instructions (2024)

References

Top Articles
Latest Posts
Article information

Author: Margart Wisoky

Last Updated:

Views: 5955

Rating: 4.8 / 5 (78 voted)

Reviews: 93% of readers found this page helpful

Author information

Name: Margart Wisoky

Birthday: 1993-05-13

Address: 2113 Abernathy Knoll, New Tamerafurt, CT 66893-2169

Phone: +25815234346805

Job: Central Developer

Hobby: Machining, Pottery, Rafting, Cosplaying, Jogging, Taekwondo, Scouting

Introduction: My name is Margart Wisoky, I am a gorgeous, shiny, successful, beautiful, adventurous, excited, pleasant person who loves writing and wants to share my knowledge and understanding with you.